Eemax SafeAdvantage NEMA 4 Electric Tankless Water Heater AP126480-EFD-N4
SafeAdvantage AP126480 126kW 480v in NEMA EnclosureSafeAdvantage is made for safety applications and has Eemax's patent-pending Parabolic Heat Design (PHD).
|
36-48kw 480v | Size: 17.42"H x 17.13"W x 10.28"D Weight: 42 lbs. |
54-126kw 480v & 32-81kw 208v |
Size: 17.42"H x 26.17"W x 10.28"D Weight: 68 lbs. |
Rated Pressure | 150psi |
UL Listing | UL 499 |
Unique Features: | Parabolic Heat Design Optic Heat Sensing Safety |
Standard Temp Setting |
90°F |
Temp Accuracy | +/- 1° at a steady flow |
Max Flow Rate | Approximately 40GPM |
Phase | Three |
NPT Fitting | 1.25" except for AP036480 and AP048480 which are 0.75" |
SafeAdvantage Model Matrix
Model number |
Application |
Voltage |
Power (kW) |
BTU | Amps per Phase |
Recommended Wire Size |
Activation |
Temperature Rise in °F (GPM) |
||||||||
3 | 4 | 6 | 7.5 | 20 | 23 | 26 | 30 | 40 | ||||||||
AP032208 N4/N4X |
EE | 208v |
32 |
109,189 | 89A | 3 AWG | 1.0 | 73 | 55 | 36 | 29 | 11 | 10 | 8 | 7 | 5 |
AP041208 N4/N4X |
EFD | 208v | 41 | 143,310 | 112A | 2 AWG | 1.0 | 93 | 70 | 47 | 37 | 14 | 12 | 11 | 9 | 7 |
AP054208 N4/N4X |
EFD | 208v | 54 | 184,256 | 150A | 1/0 AWG | 1.5 | 123 | 92 | 61 | 49 | 18 | 16 | 14 | 12 | 9 |
AP064208 N4/N4X |
EFD | 208v | 64 | 218,377 | 178A | 3/0 AWG | 1.5 | 146 | 109 | 73 | 58 | 22 | 19 | 17 | 15 | 11 |
AP081208 N4/N4X |
EFD | 208v | 81 | 276,384 | 225A | 4/0 AWG | 2.5 | 147 | 138 | 92 | 74 | 28 | 24 | 21 | 18 | 14 |
AP036480 N4/N4X | EE | 480v | 36 | 122,837 | 43A | 8 AWG | 1.0 | 82 | 61 | 41 | 33 | 12 | 11 | 9 | 8 | 6 |
AP048480 N4/N4X | EFD | 480v | 48 | 163,783 | 57.6A | 6 AWG | 1.0 | 109 | 82 | 55 | 44 | 16 | 14 | 13 | 11 | 8 |
AP054480 N4/N4X | EFD | 480v | 54 | 184,256 | 65A | 6 AWG | 1.5 | 123 | 92 | 61 | 49 | 18 | 16 | 14 | 12 | 9 |
AP072480 N4/N4X | EFD | 480v | 72 | 245,674 | 87A | 3 AWG | 2.5 | 147 | 123 | 82 | 66 | 25 | 21 | 19 | 16 | 12 |
AP096480 N4/N4X | EFD | 480v | 96 | 327,552 | 116A | 1/0 AWG | 2.5 | 147 | 147 | 131 | 109 | 33 | 29 | 25 | 22 | 16 |
AP108480 N4/N4X | EFD | 480v | 108 | 368,511 | 130A | 1 AWG | 2.5 | 147 | 147 | 123 | 98 | 37 | 32 | 28 | 25 | 18 |
AP126480 N4/N4X | EFD | 480v | 126 | 429,930 | 151A | 2/0 AWG | 2.5 | 147 | 147 | 143 | 115 | 43 | 37 | 33 | 29 | 21 |
AP144480 N4/N4X | EFD |
480v | 144 | 491,348 | 173A | 2/0 AWG | 2.5 | 147 | 147 | 147 | 131 | 49 | 43 | 38 | 33 | 24 |
AP216480 N4/N4X | EFD | 480v | 216 | 737,022 | 260A | 300 MCM |
2.5 | 147 |
147 |
147 |
147 |
74 |
64 |
57 |
49 |
37 |
AP108600 N4/N4X | EFD | 600v | 108 | 368,511 | 104A | 2 AWG | 2.5 | 147 | 147 | 123 | 98 | 37 | 32 | 28 | 25 | 18 |
AP162600 N4/N4X | EFD | 600v | 162 | 552,767 | 156A | 2/0 AWG | 2.5 | 147 | 147 | 147 | 147 | 55 | 48 | 43 | 37 | 27 |
AP216600 N4/N4X | EFD | 600v | 216 | 737,022 | 207A | 4/0 AWG |
2.5 | 147 | 147 | 147 | 147 | 74 | 64 | 57 | 49 | 37 |
Suffix Definition
EFD: Emergency Eye and Face Drench Shower
• Ships with maximum temperature setting of 90°F. Apply software update to change temperature.
• Minimum heating element activation temp is 2.5 GPM
• Interface is locked by default
EE: Emergency Eyewash
• Ships with maximum temperature setting of 90°F
• Interface is locked by default
N: NEMA 4
• Standard configuration for the SafeAdvantage. Includes NEMA 4 cabinet. NEMA 4 is the spec for being waterproof
N4X: NEMA 4X
• Includes NEMA 4X 304 stainless steel cabinet. 4X is the spec for being waterproof and corrosion-proof.
Other Optional Features
• NEMA N4X6 (spec for submersion) with 316 stainless steel enclosure
• Leak detection
• Indoor disconnect switch
• Alarm contacts
• Beacon
• Siren
• Stand Kit for freestanding installations
• Explosion Proof (Class 1 Div 1 & 2)
• Freeze Protection
• Additional options are available with custom order
Document Downloads
SpecAdvantage Specifications
SafeAdvantage Specifications
Troubleshooting
Warranty
Order Submittal Sheet (required with every SpecAdvantage/SafeAdvantage order)
Videos