Eemax XTP018208 ProSeries XTP 18kW 208V 3-phase Industrial/Commercial Tankless Water Heater
Applications
• Booster (up to 180°F) • Commercial kitchens • Dishwasher • Restaurants, wet bar • Mop sinks, utility sinks • Handwashing (both fixed-flow and variable) • Washdown processes • Recirculation loop: In accordance with NEC guidelines, the water heater is designed for a maximum continuous duty cycle of 3 hours at 100% power output. After 3 hours, the heater should be powered down for long enough for the heater and electrical infrastructure to return to ambient temperature.
Custom configurations and applications are welcome but non-refundable.
High-Performance Features
• Adaptive Stability Technology™ assesses the heater condition and adjusts unit operation to ensure a consistent and reliable output • Self-diagnostics with intelligent controls actively protect the heater depending on water conditions • 4-line, 20-character LED display provides good user interface with system and operation status and data • Control board stores error history • Built to last: Case is powder-coated galvanized steel. Stainless steel heating chambers and sheathed copper heating elements protect the heater and minimize the occurrence of rust and corrosion • Output temperature stability at +/- 1°F (+/- 0.6°C) • Powered by three phase delta, capable of supporting locations serviced by 3-phase WYE (Y) or delta power • Only one input water line (cold or hot) needed for installation • User adjustable temperature settings 60°F to 180°F (factory set output at 120°F) • Compact size for greater installation location flexibility • Includes wall mounting bracket allows for easy, flexible installation • User-adjustable activation flow rate • Thermistors on both inlet and outlet for precise temperature control • Tamper-resistant controls (hardware lockout) • IP25-rated cover prevents water intrusion within the system, for water run-off and minimal corrosion • SafeStart™ engages upon start-up to avoid dry-fire occurrence • High temperature limit switch enables safe operation
Performance Specifications
Installation info
- Sizing: Size based on performance and not electrical infrastructure. Three key factors are incoming water temperature, water volume, and desired outlet temperature.
- Electrical: Requires 3 lives and 1 ground (earth). When converting a Y (wye) configured unit to a ProSeries XTP delta-configured model, the neutral leg is not required. All Eemax Tankless Water Heaters are designed to be hardwired to a dedicated circuit breaker. Eemax tankless heaters are not supplied with a cord and plug.
- Plumbing: Pre-heated or cold water feed. The XTP series models have an internal display with thermostatic control and is capable of instantly responding to changing temperatures while providing a stable output.
- Position/Orientation: Can be mounted vertically (upright) or horizontally
Optional NEMA cabinet features
• Enclosure types: N4 (powder coated steel), N4X (304SS) N4X6 (316SS) • SK: Free standing legs. 24" legs for free standing applications • FP: Freeze protection for harsh climates, down to -30°F • EDS: non-fused electrical disconnect • FDS: fused electrical disconnect • GFCI: True RMS GFCI with digital display and reset • EP: C1D2 compliant explosion proof. Local certification required. Class Z purge and pressurization system provided with pressure switch for alarm controls. For classifications other than C1D2, please contact Eemax to discuss options. • SB: Siren and beacon audible and visual alarm. C1D2 compliant when paired with explosion proof package. • DC: Dry contact • ES: Emergency stop push button
Visible display is included with all NEMA cabinet types.
Documentation
Spec Sheet Warranty
Certifications

|
Evaluation and compliance to either Underwriters Laboratories (UL) or Intertek (ETL) under CAN/CSA-C22.2 No. 64/No. 88
|
|
Specifications of XTP model series
Model Number
|
Three Phase Voltage, Kilowatt Power Rating |
Amperage per phase |
Recommended Wire Gauge (90° C/CU) |
Temperature Rise °F at given GPMs |
1.0 |
2.0 |
3.0 |
4.0 |
5.0 |
6.0 |
7.0 |
8.0 |
9.0 |
10.0 |
XTP016480 |
480v, 16 kW |
19 |
12 AWG |
109 |
55 |
36 |
27 |
22 |
18 |
16 |
14 |
12 |
11 |
XTP018208 |
208v, 18 kW |
50 |
8 AWG |
119 |
60 |
40 |
30 |
25 |
20 |
17 |
15 |
13 |
12 |
XTP020480 |
480v, 20 kW |
24 |
10 AWG |
137 |
68 |
46 |
34 |
27 |
23 |
20 |
17 |
15 |
14 |
XTP024208 |
208v, 24 kW |
67 |
4 AWG |
† |
82 |
55 |
41 |
33 |
27 |
23 |
20 |
18 |
16 |
XTP024480 |
480v, 24 kW |
29 |
10 AWG |
† |
82 |
55 |
41 |
33 |
27 |
23 |
20 |
18 |
16 |
XTP027480 |
480V, 27 kW |
33 |
8 AWG |
† |
92 |
61 |
46 |
31 |
31 |
26 |
23 |
20 |
18 |
XTP032208 |
208V, 31.2 kW |
87 |
3 AWG |
† |
107 |
71 |
51 |
43 |
36 |
30 |
27 |
24 |
21 |
XTP036480 |
480V, 37 kW |
45 |
8 AWG |
† |
126 |
84 |
63 |
51 |
42 |
36 |
32 |
28 |
25 |
XTP048480 |
480V, 48 kW |
58 |
6 AWG |
† |
† |
109 |
82 |
66 |
55 |
47 |
41 |
36 |
33 |
XTP054480 |
480V, 54 kW |
65 |
4 AWG |
† |
† |
123 |
92 |
74 |
61 |
53 |
46 |
41 |
37 |
† Temperature electronically limited to factory preset temperature. |